3. Instruction Set
3-7
Mnemonic
Operands Function Program steps
Controllers
ES2/EX2/
EC5
SS2
SA2
SE
SX2
ANI X, Y, M, S, T, C
Connect NC contact
in series
1~3
Explanations:
1. The ANI instruction is used to connect NC contact in series.
2. Refer to instruction LD for more information on the supported firmware versions for each
modules.
Program example:
Ladder diagram:
X0X1
Y1
Instruction: Operation:
LD X1 Load NO contact X1
ANI X0 Connect NC contact X0 in series
OUT Y1 Drive Y1 coil
Ladder diagram:
X1
Y1
X15F4
L
DI
Instruction: Operation:
LD X1 Load NO contact X1
ANI X15F4 Connect NC contact X11 in series
(Suppose F4=K-4)
OUT Y1 Drive Y1 coil