3. Instruction Set
3-15
Mnemonic
Operands Function Program steps
Controllers
ES2/EX2/
EC5
SS2
SA2
SE
SX2
RST
Y, M, S, T, C, D, E,
F
Resets contacts,
registers or coils
3
Explanations:
1. Device status when RST instruction is driven:
Device Status
S, Y, M Coil and contact are set to OFF.
T, C Current value is cleared. Associated contacts or coils are reset .
D, E, F The content is set to 0.
State of designated devices remains the same when RST instruction is not executed.
1. Refer to instruction LD for more information on the supported firmware versions for each
modules.
Program example:
Ladder diagram:
X0
Y5
RST
Instruction: Operation:
LD X0 Load NO contact X0
RST Y5 Reset contact Y5
Ladder diagram:
X0
Y5E0
RST
Instruction: Operation:
LD X0 Load NO contact X0
RST Y5E0 Reset contact Y5
(Suppose E0=K0)