EasyManua.ls Logo

Delta DVP02LC-SL - Page 36

Delta DVP02LC-SL
38 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Load Cell Module DVP02LC-SL
DVP-PLC Operation Manual
34
y Program explanations
1. The PLC switches from STOP to RUN. Due to the range for analog output voltage for the
brake system is 0 to 10 VDC, we first set the voltage output mode for DVP04DA-SL to “0”
(-10 to +10 V).
2. Use the FROM instruction to read the average weight from the load cell.
3. Calculate the output value (MV) by the PID instruction and output the value to DVP04DA-SL.
y Devices
D0: Average tension value
D1: Target tension value
D50: Voltage output from DVP04DA-SL
D100: PID parameter
y Steps of PID tuning
1. Read the average value from DVP02LC-SL and store it in D110.
2. For the PID operation: PV = D110, SV = D100, PID parameter = D500. Place the result of PID
operation in D50.
3. Output D50 to CH1 of DVP04DA-SL.
4. Set the PID sampling time to 10 ms. For the parameter settings: KP = D501, KI = D502, KD =
D503.
5. After the tuning, we acquire the best parameters KP = 100, KI = 150 and KP = -5.