DVP-ES3 Series Operation Manual
4-38
_4
*1. Use shielded cables to isolate the analog input/output signal cable from other power cables.
*2. If the module is connected to a current signal, the terminals Vn and In+ (n=14) must be short-circuited.
*3. If noise in the input voltage results in noise interference with the wiring, connect the module to a capacitor
with a capacitance between 0.10.47 μF with a working voltage of 25 V.
*4. Use shielded cables to isolate the analog output signal cable from other power cables.
*5. If noise in the output voltage results in noise interference in the wiring, connect the module to a capacitor
with a capacitance between 0.1 μF0.47 μF with a working voltage of 25 V.
*6. Connect FE of the shielded cable to ground.
*7. Connect the terminal to ground.
*8. CHX-I: Every channel can work with the input wiring shown above. CHX-O: Every channel can work with the
output wiring shown above.