Chapter 12 Troubleshooting
12-7
2. If the error still occurs, contact the factory.
0052
The memories in the latched auxiliary
relays are abnormal.
1. Reset the CPU module or restore the CPU
module to its factory settings, and then download
the program and the parameters again.
2. If the error still occurs, contact the factory.
SM6 V
0054 The latched counters are abnormal.
1. Reset the CPU module or restore the CPU
module to its factory settings, and then download
the program and the parameters again.
2. If the error still occurs, please contact the factory.
SM6 V
0055
The latched 32-bit counters are
abnormal.
1. Reset the CPU module or restore the CPU
module to its factory settings, and then download
the program and the parameters again.
2. If the error still occurs, contact the factory.
SM6 V
0056
The latched special auxiliary relay is
abnormal.
1. Reset the CPU module or restore the CPU
module to its factory settings, and then download
the program and the parameters again.
2. If the error still occurs, contact the factory.
SM6 V
0059
The latched data registers are
abnormal.
1. Reset the CPU module or restore the CPU
module to its factory settings, and then download
the program and the parameters again.
2. If the error still occurs, contact the factory.
SM6 V
005D
The CPU module does not detect a
Check that the memory card is inserted correctly
SM453 V
005E
The memory card is initialized
Check whether the memory card is broken. SM453 V
0063
An error occurs when data is written to
Check whether the file path is correct or whether
the memory card is malfunctioning.
SM453 V
0064
A file in the memory card cannot be
Check whether the file path is correct, or whether
SM453 V
1950
The initialization of the Delta ASD-A2
control has not yet been completed, the
CANopen instructions cannot be
executed.
1. Check the CANopen connection cable.
2. Check if the specific slave is working properly.
3. If nothing is wrong, initialize the Delta ASD-A2
- V
2001
Not in the right mode for the ASDA-A2
while using the CANopen
communication instruction.
Check if the CANopen operation mode is correct. SM0 V
2003
The device used in the program
exceeds the device range.
Check the program, compile the program again,
and download the program again.
SM0 V
200B
The operand n or the other constant
operands K/H exceed the range.
Check the program, compile the program again,
and download the program again.
SM0 V
200C The operands overlap.
Check the program, compile the program again,
and download the program again.
SM0 V
200D
The binary to binary-coded decimal
Check the program, compile the program again,
and download the program again.
SM0 V
200E The string does not end with 00.
Check the program, compile the program again,
and download the program again.
SM0 V
2012 Incorrect division operation
Check the program, compile the program again,
and download the program again.
SM0 V
2013
The value exceeds the range of values
that can be represented by the
Check the program, compile the program again,
and download the program again.
SM0 V