Step 1: Mount the Base
deltamotion.com 3
Enclosure
If the RMC200 is installed in an electronics enclosure, the enclosure
must be large enough to dissipate the power that is being generated
by the components in the cabinet without having the air temperature
in the cabinet exceed the rating on any of the components within the
cabinet.
To ensure sufficient convection, the enclosure should provide the
following clearances:
• At least 2” between front of RMC200 and enclosure
• At least 3” between top of RMC200 and enclosure
• At least 3” plus space for wires between bottom of RMC200
and enclosure
Grounding
IMPORTANT: Make sure to properly ground the base metal.
Mounting via steel screws to a well-grounded surface such as a
metal panel will typically suffice. To ensure a robust
connection, the grounding stud on the bottom of the base may
be used. The Case pins of each module are electrically
connected to the module chassis, which will conduct to the
base chassis.
WARNING: Electrostatic Discharge (ESD): Electrostatic
discharge can cause internal damage and affect normal
operation. When handling this equipment, follow these
guidelines:
• Touch a grounded object to discharge potential static or
wear a grounding wrist strap.
• Do not touch connectors or pins on the module boards, or
electronic components inside the modules.
• Use a static-safe workstation, if possible.
• Store modules in ESD packaging when not in use.