9
ThesolarinverterhasaninsulationandgroundingmonitoringontheDCside.Theoptionscanbe
conguredintheSetupmenu“6.S->SolarISO/GND”(seepage23,section7.3.8).
Theinsulationmonitoringhastwomodes:
•ISO-ON-Error(thesolarinverterisdisconnectedfromthegridintheeventofaninsulation
fault)
•ISO-ON-Warning(thesolarinverterindicatesthefaultbutisnotdisconnectedfromthegrid).
Deltassolarinvertersarefactory-settoISO-ON-Warningmodeondelivery.
Thegroundingmonitoringhastwomodes:
•PV+grounding(groundingmonitoringofthepositivepoleofthePVgenerator)
•PV-grounding(groundingmonitoringofthenegativepoleofthePVgenerator).
Inthesemodesthesolarinverterremainsinfeed-inoperationandwillnotbedisconnectedfromthe
gridincaseofafault.Theerrormessage“PV+groundingfault”or“PV-groundingfault”willappear
onthedisplay.
IfyouneedtoconnectthepositiveornegativepoleofthePVsystemtomeetrequirementsset
outbythemodulemanufacturer,youcandothis.Earthcontinuitymustbeimplementedcloseto
theinverter.WesuggestusingDeltasgroundingkit“GroundingSetASolar”(EOE99000115).The
groundingconnectionismonitoredandshouldbeconguredintheSetupmenu(seeabove).
Alternatively,itispossibletoturnofftheinsulation-andgroundingmonitoring:
•ISO/GNDOFF.
RequiredcablecouplertypesforDCcableconnectiontoinverter:
CABLE
COUPLER
POLARITY
WIRE SIZE
2.5 MM
2
(AWG 14)
WIRE SIZE
4.0 MM
2
(AWG 12)
WIRE SIZE
6.0 MM
2
(AWG 10)
FEMALE CA-
BLE COUPLER
PLUS CODED
FEMALE CABLE
COUPLER
MINUS CODED
TYCO
ORDER
NUMBER
Plus
coupler
• •
1394462-1
Minus
coupler
• •
1394462-2
Plus
coupler
• •
1394462-3
Minus
coupler
• •
1394462-4
Plus
coupler
• •
1394462-5
Minus
coupler
• •
1394462-6