5 
VFD-B Series 
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 
5-69
10 - 04 
Derivative Control (D)   
Factory Setting: 0.00
 Settings  0.00 to 1.00 sec 
 This parameter specifies derivative control (rate of change of the input) and associated 
gain (D). With this parameter set to 1, the PID output is equal to differential time X 
(present deviation − previous deviation). It increases the response speed but it may cause 
over-compensation. 
10 - 05 
Upper Bound for Integral Control   
Factory Setting: 100
 Settings  00 to 100 %  Unit: 1 %
 This parameter defines an upper bound or limit for the integral gain (I) and therefore limits 
the Master Frequency. 
The formula is: Integral upper bound = Maximum Output Frequency (Pr.01-00) x 
(Pr.10-05). This parameter can limit the Maximum Output Frequency 
 
10 - 06 
Primary Delay Filter Time   
Factory Setting: 0.0
 Settings  0.0 to 2.5 sec  Unit: 0.1 sec
 (1) To avoid amplification of measurement noise in the controller output, a derivative 
digital filter is inserted. This filter helps in smoothing oscillations.   
(2) When Pr.02-01 is set to 01 or 02, the set point (Master Frequency) for PID control is 
obtained from the AVI external terminal (0 to +10V) or from multi-step speed. When 
Pr.02-01 is set to 00, the set point is obtained from the keypad. 
The complete PID diagram is the following: 
P
10-02
I
10-03
D
10-04
10-05
10-01
10-07
10-06
10-00
+
-
+
+
+
Setpoint
Input Freq.
Gain
PID
feedback
Integral 
gain
limit
Output 
Freq.
Limit
Digital
filter
Freq.
Command
 
 
10 - 07 
PID Output Frequency Limit   
Factory Setting: 100
 Settings  00 to 110 %  Unit: 1%
  This parameter defines the percentage of output frequency limit during the PID control. 
The formula is Output Frequency Limit = Maximum Output Frequency (Pr.01-00) X 
Pr.10-07 %. This parameter will limit the Maximum Output Frequency.