VFD-B Series 
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 
5-12
 
02 - 01 
Source of First Operation Command 
a
   Factory Setting: 00
  Settings  00  Controlled by the digital keypad 
    01  Controlled by the external terminals, keypad STOP enabled. 
    02  Controlled by the external terminals, keypad STOP disabled. 
    03  Controlled by the RS-485 communication interface, keypad 
STOP enabled. 
    04  Controlled by the RS-485 communication interface, keypad 
STOP disabled. 
02 - 14 
Source of Second Operation Command 
a
   Factory Setting: 00
  Settings  00  Controlled by the digital keypad 
    01  Controlled by the external terminals, keypad STOP enabled. 
    02  Controlled by the external terminals, keypad STOP disabled. 
    03  Controlled by the RS-485 communication interface, keypad 
STOP enabled. 
    04  Controlled by the RS-485 communication interface, keypad 
STOP disabled. 
 
When the AC drive is controlled by external terminal, please refer to Pr.02-05 for 
detailed explanations. 
 
The first /second frequency/operation command is enable/disable by Multi Function 
Input Terminals. Please refer to the setting of Pr.04-04 ~ 04-09. 
02 - 02 
Stop Method       Factory Setting: 00
  Settings  00  STOP: ramp to stop; E.F. (External Fault) : coast to stop 
    01  STOP: coast to stop; E.F. : coast to stop 
    02  STOP: ramp to stop; E.F. : ramp to stop 
    03  STOP: coast to stop; E.F. : ramp to stop 
 
The parameter determines how the motor is stopped when the AC drive receives a valid 
stop command or External Fault. 
1.  Ramp: the AC drive decelerates to Minimum Output Frequency (Pr.01-05) according to 
the deceleration time and then stops. 
2.  Coast: the AC drive stops output instantly upon command, and the motor free runs until it 
comes to a complete stop. 
3.  The motor stop method is usually determined by the characteristics of the motor load 
and the frequency of stop