Chapter 12 Descriptions of Parameter SettingsMS300
380
06-80
Fire Mode
Default: 0
Settings
0: Disable
1: Forward (counterclockwise) operation
2: Reverse (clockwise) operation
Use this parameter with multi-function input terminal setting 58 or 59, and multi-function output
terminal setting 53.
0: Fire detection is invalid.
1: The motor operates in a counterclockwise direction (U, V, W).
2: The motor operates in a clockwise direction (U, W, V).
06-81
Operating Frequency in Fire Mode
Default: 60.00
Settings
0.00–599.00 Hz
Enables fire mode (Pr.06-70 = 1 or 2) and sets the operation frequency in fire mode (Pr.06-81).
The drive operates with operation frequency in fire mode when the fire mode is enabled.
06-88
Operation Times in Fire Mode
Default: Read only
Settings
0–65535 times
Counts once when fire mode operates for 4 minutes.