Chapter 12 Description of Parameter SettingsMS300 (High Speed Model) 
 
12-05-1 
05 Motor Parameters    This parameter can be set during operation. 
 
 
Full-load Current of Induction Motor 1 (A) 
 
 
 Unit: Ampere 
 
 
  Factory Setting: #.## 
  Settings  10~120 % of drive’s rated current 
 This value should be set according to the rated current of the motor as indicated on the motor 
nameplate. The factory setting is 90 % of rated current. 
Example: The rated current of 7.5 HP (5.5 kW) is 25 A, the factory setting is 22.5 A.   
The setting range will be 2.5~30 A. (25 × 10 % = 2.5 A and 25 × 120 % = 30 A) 
 
 
Rated Power of Induction Motor 1 (kW) 
 
 
  Factory Setting: #.## 
  Settings  0~655.35 kW 
 It is used to set rated power of motor 1. Factory setting is the power value of drive. 
 
 
Rated Speed of Induction Motor 1 (rpm) 
 
 
  Factory Setting: 1710 
  Settings  0~65535 
    1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles) 
 It is used to set the rated speed of the motor according to motor nameplate. 
 
 
Pole Number of Induction Motor 1 
 
 
  Factory Setting: 4 
  Settings  2~20 
 It is used to set the number of motor poles (must be an even number). 
 Set up Pr. 01-01 and Pr. 05-03 before setting up Pr. 05-04 to make sure motor operates normally. 
 
 
Full-load Current of Induction Motor 2 (A) 
 
 
 Unit: Ampere 
 
 
  Factory Setting: #.## 
  Settings  10~120 % of drive’s rated current 
 This value should be set according to the rated frequency of the motor as indicated on the motor 
nameplate. The factory setting is 90 % of rated current.   
Example: The rated current of 7.5 HP (5.5 kW) is 25 A, the factory setting is 22.5 A.   
The setting range will be 2.5~30 A. (25 × 10 % = 2.5 A and 25 × 120 % = 30 A) 
 
 
Rated Power of Induction Motor 2 (kW) 
 
 
 
 
  Factory Setting: #.## 
  Settings  0~655.35 kW 
 It is used to set rated power of motor 2. Factory setting is the power value of drive.