5-9 Electromagnetic/Induction Noise 
There are many noises surround the Hybrid servo drive and invade it by radiation or power circuit. It may 
cause the misoperation of control circuit and even damage the 
Hybrid servo drive. Of course, that is 
a solution to increase the noise tolerance of the 
Hybrid servo drive. But it is not the best one due to 
the limit. Therefore, solve it from the outside as following will be the best. 
1.  Add surge killer on the relay or contact to suppress switching surge between ON/OFF.   
2.  Shorten the wiring length of the control circuit or serial circuit and separate from the main circuit 
wiring. 
3.  Comply with the wiring regulation for those shielded wire and use isolation amplifier for long wire. 
4.  The grounding terminal should comply with the local regulation and ground independently, i.e. not 
to have common ground with electric welding machine and power equipment. 
5.  Connect a noise filter at the input terminal of the Hybrid servo drive to prevent noise from power 
circuit. 
 
In a word, three-level solutions for electromagnetic noise are “no product”, “no spread” and “no 
receive”.