2. Wiring 
 
2-5
PI
QI
MI
PI
QI
03 13 2
-=
03 13 2
-=
SG+
SG-
SG+
SG-
SG+
SG-
SG+
SG-
03 13 3
-=
M M
M M
PO
PO
03 13 1
-=
Mater 1
Slave Slave
Mater 3
Hydraulic outlet 1
Hydraulic outlet 2
Pressure 
Command
Flow 
Command 
Pressure 
Command
Flow Command 
Combined/Divert 
Signals
When the signals are confluence, the communication will be a short circuit
When the signals are diversion, the communication becomes an open circu
            - .
 
 
;
  The wiring of main circuit and control circuit should be separated to prevent 
erroneous actions.   
;
  Please use shield wire for the control wiring and not to expose the peeled-off net in 
front of the terminal. 
;
  Please use the shield wire or tube for the power wiring and ground the two ends of 
the shield wire or tube. 
;
  Make sure that the leads are connected correctly and the AC drive is properly 
grounded. (Ground resistance should not exceed 0.1
Ω
.) 
;
  Use ground leads that comply with local regulations and keep them as short as 
possible. 
;
  Multiple VFD-VJ units can be installed in one location. All the units should be 
grounded directly to a common ground terminal, as shown in the figure below.
Ensure there are no ground loops. 
Excellen
Grounding terminals