4-36
Example: Slave is 60L/min and Master is 40L/min, so the setting is 60/40 * 100% = 150% 
For confluence of more than 2 pump, the values for the slaves must be the same. For 
example, if the total flow for a three-pump system is 200L/min, where the Master is 40L/min, 
then the two Slaves should be 80L/min. The setting of Parameter 03-14 should be 160/40 = 
400% 
a 
 
Source of frequency command 
 
Control mode  VF  FOCPG  FOCPM   
  Factory default: 0 
 
Settings  0: Digital Operation Panel 
 
  1: RS485 Communication 
 
 2~5: Reserved 
  This parameter is used for EMVJ-MF01.For detailed operation, please refer to Chapter 3 for 
tuning. 
  In a confluence system, if the Slave’s frequency command is given through the RS485 
communication, the setting value should be 1. 
a 
 
Limit for the Slave reverse depressurization torque 
 
Control mode  VF  FOCPG  FOCPM   
  Factory default: 20 
 
Settings 0~500% 
  Set the torque limit for the Slave’s reverse operation.   
 
 
Slave’s activation level 
 
Control mode  VF  FOCPG  FOCPM   
  Factory default: 50 
 
Settings 0~100% 
  This parameter setting is required only for the Master but not needed for the Slave.   
  This parameter determines the activation level for the Slave. A 100% value corresponds to the full 
flow of the Master.   
a 
 
Communication error treatment 
 
Control mode  VF  FOCPG  FOCPM   
  Factory default: 0 
 
Settings  0: Warn and keep operation 
 
  1: Warn and ramp to stop 
 
  2: Warn and coast to stop   
 
  3: No action and no display 
  This parameter is used to set the handling status of the drive when a communication timeout error 
(such as disconnection) occurs. 
a 
 
Time-out detection 
 
Control mode  VF  FOCPG  FOCPM   
  Factory default: 0.0 
 
Settings 0.0~100.0 seconds 
  This parameter is used to set the time of the time-out event for the communication and the keypad 
transmission.  
a 
 
Start-up display selection