Chapter 11 Summary of Parameter SettingsC2000 Plus
11-10
Pr. Parameter Name Setting Range Default
00-30
Master Frequency Command
Source (HAND)
0: Digital keypad
1: RS-485 communication input
2: External analog input (Refer to Pr.03-00–03-02)
3: External UP / DOWN terminal (multi-function input
terminals)
4: Pulse input without direction command
(refer to Pr.10-16 without considering direction)
5: Pulse input with direction command (refer to Pr.10-16)
6: CANopen communication card
8: Communication card (CANopen card not included)
0
00-31
Operation Command Source
(HAND)
0: Digital keypad
1: External terminals
2: RS-485 communication input
3: CANopen communication card
5: Communication card (CANopen card not included)
0
00-32 Digital Keypad STOP Function
0: STOP key disabled
1: STOP key enabled
0
00-33 RPWM Mode Selection
0: Disabled
1: RPWM mode 1
2: RPWM mode 2
3: RPWM mode 3
0
00-34 RPWM Range
0.0–4.0 kHz
Pr.00-17 = 4 kHz, 8 kHz: the setting range is 0.0–2.0
kHz
Pr.00-17 = 5–7 kHz: the setting range is 0.0–4.0 kHz
0.0
00-37 Over-Modulation Gain 80–120 100
00-48 Display Filter Time (Current) 0.001–65.535 sec. 0.100
00-49 Display Filter Time (Keypad) 0.001–65.535 sec. 0.100
00-50 Software Version (Date) Read only
Read
only