Chapter 11 Summary of Parameter SettingsC2000 Plus
11-9
Pr. Parameter Name Setting Range Default
012xh: ft
013xh: degC
014xh: degF
015xh: mbar
016xh: bar
017xh: Pa
018xh: kPa
019xh: mWG
01Axh: inWG
01Bxh: ftWG
01Cxh: psi
01Dxh: atm
01Exh: L/s
01Fxh: L/m
020xh: L/h
021xh: m3/s
022xh: m3/h
023xh: GPM
024xh: CFM
xxxxh: Hz
00-26 Maximum User-Defined Value
0: Disabled
0–65535 (when Pr.00-25 is set to no decimal place)
0.0–6553.5 (when Pr.00-25 is set to 1 decimal place)
0.00–655.35 (when Pr.00-25 is set to 2 decimal places)
0.000–65.535 (when Pr.00-25 is set to 3 decimal places)
0
00-27 User-Defined Value Read only
Read
only
00-29 LOCAL / REMOTE Selection
0: Standard HOA function
1: When switching between LOCAL and REMOTE, the
drive stops.
2: When switching between LOCAL and REMOTE, the
drive runs with REMOTE settings for frequency and
operation status.
3: When switching between LOCAL and REMOTE, the
drive runs with LOCAL settings for frequency and
operation status.
4: When switching between LOCAL and REMOTE, the
drive runs with LOCAL settings when switched to Local
and runs with REMOTE settings when switched to
Remote for frequency and operation status.
0