Chapter 11 Summary of Parameter SettingsC2000 Plus
11-30
Pr. Parameter Name Setting Range Default
05-36
Rated Speed for a Permanent
Magnet Synchronous AC Motor /
Reluctance Motor
0–65535 rpm 2000
05-37
Number of Poles for a
Permanent Magnet Synchronous
AC Motor / Reluctance Motor
0–65535 10
05-38
System Inertia for a Permanent
Magnet Synchronous AC Motor /
Reluctance Motor
0.0–6553.5 kg-cm
2
Depending
on the
motor
power
05-39
Stator Resistance for a
Permanent Magnet Synchronous
AC Motor / Reluctance Motor
0.000–65.535
0.000
05-40
Permanent Magnet Synchronous
AC Motor / Reluctance Motor Ld
0.00–655.35 mH / 0.0–6553.5 mH
0.00 /
0.0
05-41
Permanent Magnet Synchronous
AC Motor / Reluctance Motor Lq
0.00–655.35 mH / 0.0–6553.5 mH
0.00 /
0.0
05-42
PG Offset Angle for a Permanent
Magnet Synchronous AC Motor /
Reluctance Motor
0.0–360.0°
0.0
05-43
Ke Parameter of a Permanent
Magnet Synchronous AC Motor /
Reluctance Motor
0–65535 (V / krpm) 0