Chapter 11 Summary of Parameter SettingsC2000 Plus
11-31
06 Protection Parameters
Pr. Parameter Name Setting Range Default
06-00 Low Voltage Level
230V models:
Frame A–D: 150.0–220.0 V
DC
Frame E and above: 190.0–220.0 V
DC
460V models:
Frame A–D: 300.0–440.0 V
DC
Frame E and above: 380.0–440.0 V
DC
575V models: 420.0–520.0 V
DC
690V models:
450.0–660.0 V
DC
180.0
200.0
360.0
400.0
470.0
480.0
06-01 Over-Voltage Stall Prevention
0: Disabled
230V models: 0.0–450.0 V
DC
460V models: 0.0–900.0 V
DC
575V models: 0.0–920.0 V
DC
690V models: 0.0–1087.0 V
DC
380.0
760.0
920.0
1087.0
06-02
Selection for Over-Voltage Stall
Prevention
0: Traditional over-voltage stall prevention
1: Smart over-voltage stall prevention
0
06-03
Over-Current Stall Prevention
during Acceleration
230V / 460V models
Heavy duty: 0–195% (100% corresponds to the rated
current of the drive)
Super Heavy duty: 0–210% (100% corresponds to
the rated current of the drive)
575V / 690V models
Light duty: 0–125% (100% corresponds to the rated
current of the drive)
Normal duty: 0–150% (100% corresponds to the
rated current of the drive)
Heavy duty: 0–180% (100% corresponds to the rated
current of the drive)
150
150
120
120
150
06-04
Over-Current Stall Prevention
during Operation
230V / 460V models
Heavy duty: 0–195% (100% corresponds to the rated
current of the drive)
Super Heavy duty: 0–210% (100% corresponds to
the rated current of the drive)
575V / 690V models
Light duty: 0–125% (100% corresponds to the rated
current of the drive)
Normal duty: 0–150% (100% corresponds to the
rated current of the drive)
Heavy duty: 0–180% (100% corresponds to the rated
current of the drive)
150
150
120
120
150