Chapter 11 Summary of Parameter SettingsC2000 Plus
11-32
Pr. Parameter Name Setting Range Default
06-05
Acceleration / Deceleration Time
Selection for Stall Prevention at
Constant Speed
0: By current acceleration / deceleration time
1: By the first acceleration / deceleration time
2: By the second acceleration / deceleration time
3: By the third acceleration / deceleration time
4: By the fourth acceleration / deceleration time
5: By Auto-acceleration / auto-deceleration
0
06-06
Over-Torque Detection Selection
(OT1)
0: No function
1: Continue operation after over-torque detection
during constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection
during RUN
4: Stop after over-torque detection during RUN
0
06-07
Over-Torque Detection Level
(OT1)
10–250%
(100% corresponds to the rated current of the drive)
120
06-08
Over-Torque Detection Time
(OT1)
0.0–60.0 sec.
0.1
06-09
Over-Torque Detection Selection
(OT2)
0: No function
1: Continue operation after over-torque detection
during constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection
during RUN
4: Stop after Over-torque detection during RUN
0
06-10
Over-Torque Detection Level
(OT2)
10–250%
(100% corresponds to the rated current of the drive)
120
06-11
Over-Torque Detection Time
(OT2)
0.0–60.0 sec.
0.1
06-12 Current Limit
230V / 460V models:
0–195% (100% corresponds to the rated current
of the drive)
575V / 690V models:
0–250% (100% corresponds to the rated current
of the drive)
190
170
06-13
Electronic Thermal Relay
Selection 1 (Motor 1)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disabled
2
06-14
Electronic Thermal Relay Action
Time 1 (Motor 1)
30.0–600.0 sec.
60.0