Chapter 11 Summary of Parameter SettingsC2000 Plus
11-36
Pr. Parameter Name Setting Range Default
188: Load estimation error (TLAT)
189: Inertia estimation error (JsAT)
190: Bandwidth estimation error (BWAT)
191: Positioning failure during estimation (ATPF)
192: Homing deviation is too large (HmOE)
193: Cleaning multi-turn data failure (CMTE)
195: ASR AT process is too short (ATTv)
06-23 Fault Output Option 1 0–65535 (refer to bit table for fault code)
0
06-24 Fault Output Option 2 0–65535 (refer to bit table for fault code)
0
06-25 Fault Output Option 3 0–65535 (refer to bit table for fault code)
0
06-26 Fault Output Option 4 0–65535 (refer to bit table for fault code)
0
06-27
Electronic Thermal Relay
Selection 2 (Motor 2)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disabled
2
06-28
Electronic Thermal Relay Action
Time 2 (Motor 2)
30.0–600.0 sec.
60.0
06-29
PTC Detection Selection / PT100
Motion
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
0
06-30 PTC Level / KTY84 Level 0.0–100.0%
50.0
06-31
Frequency Command at
Malfunction
0.00–599.00 Hz
Read
only
06-32 Output Frequency at Malfunction 0.00–599.00 Hz
Read
only
06-33 Output Voltage at Malfunction 0.0–6553.5 V
Read
only
06-34 DC Bus Voltage at Malfunction 0.0–6553.5 V
Read
only
06-35 Output Current at Malfunction 0.0–6553.5 Amp
Read
only
06-36 IGBT Temperature at Malfunction -3276.7–3276.7°C
Read
only
06-37
Capacitance Temperature at
Malfunction
-3276.7–3276.7°C
Read
only
06-38 Motor Speed at Malfunction -32767–32767 rpm
Read
only
06-39 Torque Command at Malfunction -32767–32767%
Read
only
06-40
Status of the Multi-Function Input
Terminal at Malfunction
0000h–FFFFh
Read
only