Chapter 11 Summary of Parameter SettingsC2000 Plus
11-37
Pr. Parameter Name Setting Range Default
06-41
Status of the Multi-Function
Output Terminal at Malfunction
0000h–FFFFh
Read
only
06-42 Drive Status at Malfunction 0000h–FFFFh
Read
only
06-44 STO Latch Selection
0: STO latch
1: STO no latch
0
06-45
Output Phase Loss Detection
Action (OPHL)
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
3
06-46
Detection Time for Output Phase
Loss
230V / 460V models: 0.000–65.535 sec.
575V / 690V models: 0.000–65.535 sec.
3.000
0.500
06-47
Current Detection Level for
Output Phase Loss
0.00–100.00%
1.00
06-48
DC Brake Time for Output Phase
Loss
0.000–65.535 sec.
0.000
06-49 Lvx Auto-Reset
0: Disabled
1: Enabled
0
06-50
Time for Input Phase Loss
Detection
0.00–600.00 sec. 0.20
06-51
Capacitance oH Warning Level
(Applied to 230V / 460V Models)
0.0–110.0 degree
Depending
on the
model
power
06-52
Ripple of Input Phase Loss
230V models: 0.0–160.0 V
DC
460V models: 0.0–320.0 V
DC
575V models: 0.0–400.0 V
DC
690V models: 0.0–480.0 V
DC
30.0
60.0
75.0
90.0
06-53
Input Phase Loss Detection
Action (OrP)
0: Fault and ramp to stop
1: Fault and coast to stop
0
06-55 Derating Protection
0: Auto-decrease carrier frequency and limit output
current
1: Constant carrier frequency and limit output current
2: Auto-decrease carrier frequency
0
06-56 PT100 Voltage Level 1 0.000–10.000 V 5.000
06-57 PT100 Voltage Level 2 0.000–10.000 V 7.000
06-58
PT100 Level 1 Frequency
Protection
0.00–599.00 Hz 0.00
06-59
PT100 Activation Level 1
Protection Frequency Delay Time
0–6000 sec. 60
06-60
Software Detection GFF Current
Level
0.0–200.0% 60.0