Chapter 11 Summary of Parameter SettingsC2000 Plus
11-47
Pr. Parameter Name Setting Range Default
2: Profibus-DP Slave
3: CANopen Slave / Master
5: EtherNet / IP Slave
6: EtherCAT (applied to 230V / 460V models)
12: PROFINET (applied to 230V / 460V models)
09-61
Firmware Version of Communication
Card
Read only Read only
09-62 Product Code Read only Read only
09-63 Error Code Read only Read only
09-70
Communication Card Address
(for DeviceNet or PROFIBUS)
DeviceNet: 0–63
Profibus-DP: 1–125
1
09-71
Communication Card Speed Setting
(for DeviceNet)
Standard DeviceNet:
0: 125 Kbps
1: 250 Kbps
2: 500 Kbps
3: 1 Mbps (Delta only)
Non-standard DeviceNet: (Delta only)
0: 10 Kbps
1: 20 Kbps
2: 50 Kbps
3: 100 Kbps
4: 125 Kbps
5: 250 Kbps
6: 500 Kbps
7: 800 Kbps
8: 1 Mbps
2
09-72
Additional Settings for
Communication Card Speed (for
DeviceNet)
0: Standard DeviceNet
In this mode, the baud rate can only be 125
Kbps, 250 Kbps or 500 Kbps in standard
DeviceNet speed
1:
Non-standard DeviceNet
In this mode, DeviceNet baud rate can be
same as that for CANopen (0–8).
0
09-74 Communication Card Control Flag
bit0: set the EDS identity definition of EIP card
bit0 = 0: identify EIP card by the drive’s family
bit0 = 1: identify EIP card by the drive’s series
1
09-75
Communication Card IP
Configuration (for EtherNet)
0: Static IP
1: Dynamic IP (DHCP)
0
09-76
Communication Card IP Address 1
(for EtherNet)
0–65535 0