Chapter 11 Summary of Parameter SettingsC2000 Plus
11-56
Pr. Parameter Name Setting Range Default
11-22
Flux Weakening Curve for Motor 2
Gain Value
0–200% 90
11-23
Flux Weakening Area Speed
Response
0–150% 65
11-24 APR Gain 0.00–40.00 Hz (IM) / 0–100.00 Hz (PM) 5.00
11-25
Gain Value for the APR Feed
Forward
0–100 90
11-26
APR Feedforward Low Pass Filter
Bandwidth
0.00–655.35 sec. 10.00
11-27 Maximum Torque Command 0–500% 100
11-28 Torque Offset Source
0: Disabled
1: Analog signal input (Pr.03-00)
2: Pr.11-29
3: Controlled through external terminals
(Pr.11-30–11-32)
0
11-29 Torque Offset Setting -100.0–100.0% 0.0
11-30 High Torque Offset -100.0–100.0% 30.0
11-31 Middle Torque Offset -100.0–100.0% 20.0
11-32 Low Torque Offset -100.0–100.0% 10.0
11-33 Torque Command Source
0 : Digital keypad
1 : RS-485 communication (Pr.11-34)
2: Analog signal input (Pr.03-00–03-02)
3: CANopen
5: Communication card
0
11-34 Torque Command -100.0–100.0% (Pr.11-27 set value = 100%) 0.0
11-35 Torque Command Filter Time 0.000–1.000 sec. 0.000
11-36 Speed Limit Selection
0: Set by Pr.11-37 (Forward speed limit) and Pr.11-
38 (reverse speed limit)
1: Set by Pr.00-20 (Master frequency source
command) and Pr.11-37, Pr.11-38
2: Set by Pr.00-20 (Master frequency source
command).
0
11-37
Forward Speed Limit (Torque
Mode)
0–120% 10
11-38
Reverse Speed Limit (Torque
Mode)
0–120% 10
11-39
Zero Torque Command Mode
Selection
0: Torque mode
1: Speed mode
0
11-40
Position Control Command
Source
0: Input from internal register
1: Input from external pulse
0