Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-02-25
  Once the output speed (frequency) reaches desired speed (frequency), if the corresponding multi-
function output terminal is set to 3–4 (Pr.02-13, Pr.02-14, Pr.02-36 and Pr.02-37), this multi-
function output terminal is “closed”. 
 
 
 
02-32 
Brake Delay Time 
 
 
   
 
Default: 0.000 
 
 
Settings 0.000–65.000 sec. 
 When the AC motor drive runs after the setting delay time of Pr.02-32, the corresponding multi-
function output terminal (12: mechanical brake release) is “closed”. This function must be used 
with DC brake.