Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-02-26
 This parameter is invalid if it is used without DC brake. Refer to the following operation timing. 
 
 
 
02-33 
Output Current Level Setting for Multi-Function Output Terminal 
 
 
   
 Default: 0 
 
 
Settings 0–100% 
 When the drive outputs current higher than or equal to Pr.02-33 ( ≥ Pr.02-33), the multi-function 
output parameters active (Pr.02-13, Pr.02-14, Pr.02-16, and Pr.02-17 are set to 27). 
 When the drive outputs current lower than Pr.02-33 (< Pr.02-33), the multi-function output 
parameters active (Pr.02-13, Pr.02-14, Pr.02-16, and Pr.02-17 are set to 28). 
 
02-34 
Output Frequency Setting for Multi-Function Output Terminal 
 
 
   
 Default: 3.00 
 
 
Settings 0.00–599.00 Hz  
(Motor speed when using PG Card) 
 When the drive outputs frequency higher than or equal to Pr.02-34 (actual output frequency H ≥ 
Pr.02-34), the multi-function terminals activate (Pr.02-13, Pr.02-14, Pr.02-16 and Pr.02-17 are set 
to 29). 
 When the drive outputs frequency lower than Pr.02-34 (actual output frequency H < Pr.02-34), the 
multi-function terminals activate (Pr.02-13, Pr.02-14, Pr.02-16 and Pr.02-17 are set to 30). 
 
02-35 
External Operation Control Selection after Reset and Reboot 
 
 
   
 Default: 0 
 
 
Settings 0: Disabled 
1: Drive runs if the RUN command remains after reset or reboot 
Setting 1: The drive automatically executes the RUN command under the following 
circumstances, pay extra attention on this. 
  Status 1: After the drive is powered on and the external terminal for RUN stays ON, the drive   
runs.