Chapter 12 Descriptions of Parameter SettingsMS300
386
07-12
Speed Tracking during Start-up
Default: 0
Settings
0: Disable
1: Speed tracking by the maximum output frequency
2: Speed tracking by current frequency command at start
3: Speed tracking by the minimum output frequency
Speed tracking is suitable for punch, fans and other large inertia loads. For example, a
mechanical punch usually has a large inertia flywheel, and the general stop method is coast to
stop. If it needs to be restarted again, the flywheel may take 2–5 minutes or longer to stop. This
parameter setting allows you to start the flywheel operating again without waiting until the
flywheel stops completely.
07-13
dEb Function Selection
Default: 0
Settings
0: Disable
1: dEb with auto-acceleration / auto-deceleration, the drive does not output
the frequency after the power is restored.
2: dEb with auto-acceleration / auto-deceleration, the drive outputs the
frequency after the power is restored.
3: dEb low-voltage control, then the drive’s voltage increases to 350 V
DC
/
700 V
DC
and ramps to stop after low frequency
4: dEb high-voltage control of 350 V
DC
/ 700 V
DC
, and the drive ramps to stop
dEb (Deceleration Energy Backup) lets the motor decelerate to stop when momentary power
loss occurs. When the power loss is instantaneous, use this function to let the motor decelerate
to zero speed. If the power recovers at this time, the drive restarts the motor after the dEb return
time.
Lv return level: Default value depends on the drive power model.
Models for frame A, B, C, D = Pr.06-00 + 75 V (575V models) / 60 V (460V models) / 30 V (230V
models)
Models for frame E and above = Pr.06-00 + 80 V / 40 V (230V models)
Lv level: Default is Pr.06-00.
During dEb operation, other protection, such as ryF, ov, oc, occ, and EF may interrupt it, and
these error codes are recorded.
The STOP (RESET) command does not work during the dEb auto-deceleration, and the drive
continues decelerating to stop. To make the drive coast to stop immediately, use another
function (EF) instead.
The B.B. function does not work when executing dEb. The B.B. function is enabled after the dEb
function finishes.
Even though the Lv warning does not display during dEb operation, if the DC bus voltage is
lower than the Lv level, MO = 10 (Low voltage warning) still operates.
The following explains the dEb action:
When the DC bus voltage drops below the dEb setting level, the dEb function starts to work (soft

Table of Contents

Other manuals for Delta VFD9A0MS43ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD9A0MS43ANSAA and is the answer not in the manual?

Delta VFD9A0MS43ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD9A0MS43ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals