Small fog flow coming out
from nozzle
Too low battery level or
exaust
Bag in Reserve or
Empty
No Mains power
Disturbance / interference
or potential dierences
between devices
This condition is normal and can happen on
first installation, it will completely disappear
in a while when the unit will become
completely hot.
Replace Battery
Error on thermocouple, fuse cable, resistor.
Please refer to technical service
Check mains power or F4 fuse
In the evenience of high noise on mains
power (lightings) an error while reading
thermocouple values can occur.
Execute recovery (Paragraph 16).
If even recovery fails the unit may be faulty
In very large installations or with more than
one fog units connected to the same alarm
panel, a mains power dierence can occur,
in that evenience the units have to be
decoupled.
Replace fluid Bag
Switch o the unit and verify the correct insertion
on J8 connector
Error in the thermal loop
Heater Temperature too
high or thermocouple error
RED Led ON (Fault)
All units are 100% tested
so a small ammount
of fluid could be still in
the warming unit.
Switch o the unit and clean air holes Poor ventilation
RED Led ON (Error)
ACTION/SIGNAL FOUND POSSIBLE CAUSE POSSIBLE SOLUTION