Blast chiller Service Manual
13
Rev 07/04/2015
P22 defrost type
0 = electric (defrost on relay)
1 = hot gas (defrost compressor and relay on)
2 = air (evaporator fan on)
2
P23 defrost end temperature (with reference to the evaporator
probe)
8
P24 maximum defrost duration 10
P25 defrost interval during storage; see also P26
0 = intermittent defrosting will never be activated (only the first
will be activated)
6
P26 first defrost delay from start of storage; see also P25 1
P27 defrosting at start of chilling and freezing
1 = YES
0
P28 drip-drain duration 2
P29 resetting of compressor protections at start of defrosting (only
if P22 = 1)
1 = YES
0
P30 elapsed time between the defrost request and switching on the
compressor (only if P22 = 1 and providing that the compressor
is off when the defrost is requested); see P31 (7) (8)also
30
P31 elapsed time between the defrost request and activation of the
solenoid valve (only if P22 = 1 and on condition that the
compressor is off when defrosting is requested); see also P30
0
P32 temperature above which the evaporator fan is switched off
during storage (with reference to the evaporator probe)
3
P33 P32 differential 1
P34 evaporator fan activity during defrosting (only if P22 = 0 or 1)
0 = on
1 = off
0
P35 evaporator stop time after dripping 3
P36 temperature above which the evaporator fan is switched off
(with reference to the cabinet probe)
90
P37 effect caused by activation of microport input on evaporator
fan
0 = no effect
1 = the evaporator fan will be switched off
1
P38 microport input contact type
0 = NA (input active with contact closed)
1 = NC (input active with contact open)
1
P39 micro port input alarm delay 0
P40 high pressure input contact type
0 = NA (input active with contact closed)
1 = NC (input active with contact open)
0
P41 high pressure input alarm delay 120