EasyManua.ls Logo

Detcon 240 - Serial Input Gas Sensors; Figure 5 Control Board Layout

Detcon 240
33 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
240 Operators Manual
Model 240 Operator Manual Rev. 1.8 Page 7 of 29
Ribbon Cable to LCD
Ribbon Cable to
Mother Board
Ni-Cad
Battery
AUXAUX
RS-485 Input for
Gas Sensor
SW1 - Options
4 - Password Protection
3 - Not Used
2 - 600/700 Series Sensors or
Mod 10 Controlers
1 - Analog/Serial
Figure 5 Control Board Layout
4.2.4 Serial Input Gas Sensors
When connecting serial input gas sensors such as the Detcon 600 Series, terminate the 3 conductors from
the serial cable in the following manner. Terminate A and B on the Control PCB at connector J7 shown in
Figure 5. If applicable, the shield wire can be terminated on the Mother Board at JP1 the RS-485 Jumper
labeled ‘SHLD TO GND’ (refer to
Figure 4).
Note: Serial sensor polling requires switch SW1-1 on the Control PCB to be in the “ON” position. If
polling 600 or 700 Series Sensors, SW1-2 must be in the “OFF” position. If polling Mod 10 Controllers,
SW1-2 must be in the “ON” position (See
Figure 5).
NOTE: If VDC power for the Detcon Series 600 sensor is not available at the sensor location, then it can
be provided via the + and – pins of channels 1 and 2 on the motherboard. The RS-485 wiring should be a 2
conductor, shielded twisted pair (Belden P/N 9841 is recommended).

Table of Contents

Related product manuals