EN-10 451905.66.01a · FD 0102 www.glendimpex.de
English DHW 300 - DHW 300+
Solar
Selection
Off
Bivalent
Sol
Choice of additional heat source
Off: (no add. heat source)
Bivalent: 2nd heat generator, e.g. oil, gas or wood boiler
Sol: Thermal solar energy system
Switch-on difference
6 K ... 8K ... 10 K
Sets the temperature difference between the collector and cylinder
temperature at which the solar pump should be switched on
Switch-off difference
2 K ... 4K ... 6 K
Sets the temperature difference between the collector and cylinder
temperature at which the solar pump should be switched off
Max. cylinder temp.
60 °C ... 65 °C ... 85 °C
Sets the maximum cylinder temperature that is permissible when
solar gain is available
Max. collector temp.
125 °C ... 130 °C ... 135 °C
Sets the maximum permissible temperature on the collector
(only visible for devices with additional heat exchanger and OFF or Bivalent selected)
2nd heat genera-
tor
Selection
Off
Bivalent
Sol
Choice of additional heat source
Off: (no add. heat source)
Bivalent: 2nd heat generator, e.g. oil, gas or wood boiler
Sol: Thermal solar energy system
Bivalence temperature
-8 °C ... 10 °C ... 15 °C
Limit temperature for the 2nd heat generator. The heat pump is
blocked below this temperature
Photovoltaic
Electric heater
Yes
No
Activates the electric heater (parallel to the heat pump) in photovol-
taic mode
Set temperature
35 °C ... 45 °C ... 60 °C
Entry of the domestic hot water setpoint, which is active when pho-
tovoltaic inlet is connected. The increased setpoint is also active if
the air intake temperature does not allow the heat pump to operate.
In this case, the request is processed with the electric heating ele-
ment or, where present, the 2nd heat generator.
Information
Operating status
Cylinder top Display of the cylinder temperature top (R3)
Cylinder bottom Display of the cylinder temperature bottom (R5)
Air inlet Display of the air temperature (R1)
Collector temp. Display of the collector temperature (R13 only on models with addi-
tional heat exchanger and Sol selected as 2nd heat generator)
Current setpoint Displays the current domestic hot water setpoint
Defrost sensor Display the defrost (only on models with defrost)
Fan Shows the switching status of the fan
Compressor Shows the switching status of the compressor
Electric heater Shows the switching status of the electric heater
Power Shows the calculated power consumption of the device
Operating mode Displays the current operating mode
Runtimes
Unit Displays the operating hours
Fan Shows the runtime of the fan
Compressor Shows the runtime of the compressor
Electric heater Shows the runtime of the electric heater
Soft. vers.
Shows the software version
Hardware
Shows the hardware version
Serial number
Shows the serial number
Service
Enter password
Password-protected area for after-sales service
Menu block Menu item Parameter Value Description