7 Parameterization of the switching thresholds
Important notes for parameterization
• Use a VDE-insulated screwdriver according to EN 60900 to press the SET button.
• The switching threshold and acknowledgement must be set correctly in order to ensure safe operation;
this responsibility lies with the user.
• To determine the switching thresholds, the number of pole pairs must be taken into account:
• f [Hz]= n [U/min] / 60 x number of pole pairs
• Example: 5000 rev/min x 3 (number of pole pairs) / 60 = 250Hz
• During parameterization, the output contacts are switched-off.
• The parameters are not saved by voltage break or break of the parameterization for longer than 20s.
• Frequency of (V-LIMIT 2 -10%) must be higher than (V-LIMIT 1).
• On automatic acknowledgement must be V-LIMIT 1 ≥ 1,1Hz .
• The monitoring of a minimum speed can be deselected. In this case, the lowest frequency for V-LIMIT 1
should be selected. There is no distance to keep to V-LIMIT 2. The output contacts remain closed at
standstill.
Table of frequencies
These frequencies can be set as switching thresholds.