DN3PD1
Function description
8 18-09-27 / 33pd02-V0743
4 Function description
The two-channel evaluation unit of the safety switchgear module measures the frequency of the effective rotat-
ing field of the motor at the measuring terminals L1, L2, L3.
If the parameterized switching threshold frequencies are exceeded or undershot (V-LIMIT 1 and V-LIMIT 2), or an
internal or external fault exists, the enabling current paths 13/14, 23/24 open immediately. The device is in safe
switching state.
The monitoring of V-LIMIT 1 can be deselected. Then the output contacts remain closed at standstill.
Asynchronous motors have a load-dependent slip between the motor speed and the rotating field frequency. This
must be observed by the configuration of the switching threshold (V-LIMIT 1 and V-LIMIT 2).
Switching threshold
Two switching thresholds are configurable.
V-LIMIT 1: minimum speed
If V-LIMIT 1 is undershot, the output contacts (13-14 / 23-24) switch off.
They switch on again after the acknowledgment via the acknowledgment input Q.
"Function diagram".
V-LIMIT 2: Maximum speed
If V-LIMIT 2 is exceeded, the output contacts (13-14 / 23-24) switch off.
They switch on again after the acknowledgment via the acknowledgment input Q, if V-LIMIT 2 (minus hysteresis)
is undershot.
Switching on takes place at the earliest after 0.5 seconds. (see chapter minimum switch-off time)
Start-up monitoring
The startup monitoring tA is a time limit within which the actual speed must be greater than V-LIMIT 1. If the mini-
mum speed is not reached during this time, the enable current path opens again.
The start-up monitoring time is fixed and is 60s. It is not retriggerable, it cannot be restarted while it is running.
The start-up monitoring time starts
In case of manual acknowledgment: with the falling edge of the acknowledge signal
In case of automatic acknowledgment: if the actual speed is> 1Hz
Minimum switch-off time
The minimum switch-off time tmin is the time that the enable current path is at least open after triggering before it
switches on again. It is 0.5s.
Acknowledge function
With the acknowledgment function, the enable current path is switched on again after a shutdown due to
underspeed or overspeed.
The acknowledgment takes place via the input Q.
Automatic or manual acknowledgment is possible.
With automatic acknowledgment, the Q input must always be connected to 24V DC.
A manual acknowledgment takes place after a falling signal edge at the input Q (t
Q ≥ 200ms and ≤ 10s).