Symptom Cause
Solution
G
The condenser fan(s) do not work.
Condenser fan(s) blocked or faulty.
• Electronic control faulty.
• Terminals disconnected.
Check the causes of the block and x or replace the condenser fan.
Check the condenser fan + and - outputs in the electronic control, and replace the electronic con-
trol if there are no (+) and (-) outputs.
• Connect the terminals in the condenser fan.
H
The unit works but does not cool.
• The compressor does not work.
• Unit with no load.
• Blockage in the circuit.
Compressor electronic module defective or
poor connection.
Pressure switch defective or terminals
poorly connected.
Relay or cable relay defective or
terminals poorly connected.
• Poor terminal connection.
• Proceed in accordance with section L.
Vacuum deair for 30 minutes and introduce the established load of R134a in the circuit.
Check the load and the pressures; whenever below 0.5 kg with the unit running, clean the
circuit or replace the blocked component.
Replace the compressors electronic module or check terminals.
Replace the pressure switch or check terminals.
Replace the relay or check cable and terminals.
Correctly check the components terminals in accordance with the attached wiring diagram.
I
The unit does not cool enough.
• Excess or lack of gas load.
• Condenser/electro grille dirty.
Condenser fan(s) defective.
Condenser fan(s) with polarity inverted.
Check pressure, at - temperature - pressure as a maximum reference must be 2.6 bars in low
pressure and 12 bars in high pressure at an outside temperature of 35ºC.
• Clean condenser/grille.
• Replace the condenser fan(s).
Check that the air is discharged to the outside; if it is not, invert the connector connection.
J
The blower does not work.
• Electronic control failure.
Blower defective or terminals disconnected.
Check current output in electronic control, and replace if there is no + and - output (accessed by
taking down the control panel).
• Replace the blower or connect terminals.
K
The unit does not respond to the user
selection orders.
Electronic control or control panel faulty.
• Replace the electronic control or control panel (accessed by taking down the control panel).