Table 32: Troubleshooting ECL Device Symptoms
Symptom Possible Cause Solution
Device does not com-
municate on the L
ON-
W
ORKS MS/TP
network
The device does not
have power / poor-
quality power.
See Power Supply Requirements for 24V Controllers on page 61.
Cut or broken wire. Isolate the location of the break and pull a new cable.
The maximum num-
ber of devices on a
data bus segment has
been exceeded.
Use a repeater to extend the BACnet data bus. See Network Cables on page 55.
Absent or incorrect
supply voltage
1. Check if the device is showing the 'Poor Power Quality' status code (for 24V
controllers). See Table 35 for a list of fault codes.
2. Check power supply voltage between 24VAC/DC ±15% and 24V COM pins
and ensure that it is within acceptable limits (for 24V controllers).
3. Check for tripped fuse or circuit breaker.
Overloaded power
transformer (for 24V
controllers)
1. Check if the device is showing the 'Poor Power Quality' status code. See Table
35 for a list of fault codes.
2. Verify that the transformer used is powerful enough to supply all controllers.
See Transformer Selection and Determining the Maximum Power Run Length on
page 61.
Network not wired
properly
Double check that the wire connections are correct.
Absent or incorrect
network termination
Check the network termination(s).
Too many Allure EC-
Smart-Vue sensors
are providing network
access
Disable the Net to Subnet Port Settings jumpers on all controllers. If communica-
tions are re-established, re-enable only a few Allure EC-Smart-Vue sensors to
have network access.
The STATUS LED is
blinking
The device has auto-
diagnosed a fault con-
dition
See Table 33 for a list of fault codes.
Controller is powered
but does not turn on
Fuse has blown (for
24V controllers)
Disconnect the power. Check the fuse integrity. Reconnect the power.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Distech Controls ECL/ECB-203 Series and is the answer not in the manual?

Distech Controls ECL/ECB-203 Series Specifications

General IconGeneral
BrandDistech Controls
ModelECL/ECB-203 Series
CategoryController
LanguageEnglish

Related product manuals