Operating instructions cod. 1592001300
1592001300 XC440C gb r1.0 07.06.2004.doc rel. 1.0
Pa
g
e
26 / 28
20. Default value
Name
°C °F bar PSI
Level
Description Range
SEtC
-18,0
0
2,3 33 -- Set point for compressors LSE÷HSE
SEtF
35,0
95
15,1 220 -- Set point for fans LSF÷HSF
OA1
CPr CPr CPr CPr Pr2 Outputs 1 configuration CPr(0) - FAn(1) - StP(2) - ALr(3) - LIn(4) -
nu(5)
OA2
CPr CPr CPr CPr Pr2 Outputs 2 configuration CPr(0) - FAn(1) - StP(2) - ALr(3) - LIn(4) -
nu(5)
OA3
CPr CPr CPr CPr Pr2 Outputs 3 configuration CPr(0) - FAn(1) - StP(2) - ALr(3) - LIn(4) -
nu(5)
OA4
CPr CPr CPr CPr Pr2 Outputs 4 configuration CPr(0) - FAn(1) - StP(2) - ALr(3) - LIn(4) -
nu(5)
CtyP
SPo SPo SPo SPo Pr2 Compressor type SPo(0) - dPo(1) - Scr(2)
StP
CL CL CL CL Pr2 Valve outputs polarity OP(0) - CL(1)
PC1
25 25 25 25 Pr2 Power of compressor 1 0 ÷ 255
PC2
25 25 25 25 Pr2 Power of compressor 2 0 ÷ 255
PC3
25 25 25 25 Pr2 Power of compressor 3 0 ÷ 255
PC4
25 25 25 25 Pr2 Power of compressor 4 0 ÷ 255
FtyP
404 404 404 404 Pr2 Freon Type r22(0) - 404(1) - 507(2) - 134(3) - 717(4)
rty
db db db db Pr2 Type of regulation db(0) - Pb(1)
Sty
yES yES yES yES Pr2 Compressor rotation no(0) - yES(1)
rot
yES yES yES yES Pr2 Fans rotation no(0) - yES(1)
PbC
Cur Cur Cur Cur Pr2 Probe 1 setting Cur(0) - Ptc(1) - ntc(2)
PA04
0,5 7 0,5 7 Pr2 Adjustment of read out for the Probe
at 4mA
(0.0 ÷ PA20)BAR (0 ÷ PA20)PSI
PA20
12,0 174 12,0 174 Pr2 Adjustment of read out for the Probe
at 20mA
(PA04 ÷ 51.0)BAR (PA04 ÷ 750)PSI
CAL
0 0 0 0 Pr2 Probe calibration (dEU=bar o °C) -12.0 ÷ 12.0 (dEU=PSI
o °F) -20 ÷ 20
i1C
cL cL cL cL Pr2 Configurable digital input polarity OP(0) - CL(1)
i1F
ES ES ES ES Pr2 Configurable digital input polarity
functions
ES(0) - OFF(1) - LL(2)
did
0 0 0 0 Pr2 Configurable digital input delay 0 ÷ 255 (min.)
ALIP
CL CL CL CL Pr2 Alarm input for compressors and fans
polarity
OP(0) - CL(1)
ALMr
no no no no Pr2 Manual reset of alarms for
compressors and fans
no(0) - yES(1)
dEU
°C °F bar PSI Pr2 Default measurement unit for
displaying
Bar(0) - °C(1) - PSI(2) - °F(3)
rES
dE in dE in Pr2 Resolution for °C and bar in(0) - dE(1)
rELP
rEL rEL rEL rEL Pr2 Pressure displaying rEL(0) - AbS(1)
Pdb
4 8 0.5 7 Pr2 Proportional band or neutral zone
width
(BAR) 0.1÷10.0 (°C) 0.1÷30.0
(PSI) 1÷80 (°F) 1÷50
ESC
0 0 0 0 Pr2 Energy saving value for compressors (BAR) -20.0÷20.0 (°C) -50.50.0
(PSI) -300÷300 (°F) -90÷90
OnOn
5 5 5 5 Pr2 Minimum time between 2 following
switching ON of the same compressor
0 ÷ 255 (min.)
OFOn
2 2 2 2 Pr2 Minimum time between the switching
off of a compressor and the following
switching on
0 ÷ 255 (min.)