1592017000 XLR 130-170 GB r2.0 23.03.2015 XL130 - XLR170 18/20
16. DEFAULT SETTING VALUES
Label
Name
Range
XLR130
XLR170
Level
REGULATION
Set
Set point
LS÷US
3.0
-5.0
---
Hy
Differential
0,1÷25,5 °C / 1÷45°F
2.0
2.0
Pr1
LS
Minimum set point
-50,0°C÷SET / -58°F÷SET
-10.0
-30,0
Pr2
US
Maximum set point
SET ÷ 110°C / SET ÷ 230°F
20.0
20.0
Pr2
OdS
Outputs activation delay at start up
0÷255 min.
0
0
Pr2
cco
Compressor configuration
SE; AL
SE
SE
Pr2
AC
Anti-short cycle delay
0÷30 min.
1
1
Pr1
Ac1
Second compressor start up delay
0÷255 sec.
0
0
Pr2
CCt
Compressor ON time during fast freezing
0 ÷ 23h 50 min.
0.0
0.0
Pr2
COn
Compressor ON time with faulty probe
0÷255 min.
15
15
Pr2
COF
Compressor OFF time with faulty probe
0÷255 min.
30
30
Pr2
CH
Kind of action
CL; Ht
cL
- - -
Pr2
DISPLAY
CF
Temperature measurement unit
°C ÷ °F
°C
°C
Pr2
rES
Resolution (integer/decimal point)
in ÷ de
dE
dE
Pr1
Lod
Local display
P1 ÷ 1r2
P1
P1
Pr2
DEFROST
tdF
Defrost type
rE, rT, in
- - -
rE
Pr2
EdF
Defrost mode
rtc, In, Sd
in
in
Pr2
SdF
Set point for SMART DEFROST
-30 ÷ +30°C / -22÷+86°F
0
0
Pr2
dtE
Defrost termination temperature (1°Evaporator)
-50,0÷110°C /-58÷230°F
8.0
8.0
Pr2
dtS
Defrost termination temperature (2°Evaporator)
-50,0÷110°C / -58÷230°F
- - -
8.0
Pr2
IdF
Interval between defrost cycles
1÷120h
8
8
Pr1
MdF
(Maximum) length for 1° defrost
0÷255 min.
20
20
Pr1
MdS
Maximum) length for 2° defrost.
0÷255 min.
-
0
Pr2
dFd
Displaying during defrost
rt, it, SEt, dEF, dEG
it
it
Pr2
dAd
MAX display delay after defrost
0÷255 min.
30
30
Pr2
dSd
Start defrost delay
0÷99 min.
- - -
0
Pr2
Fdt
Draining time
0÷60 min.
- - -
0
Pr2
dPO
First defrost after start up
n ÷ y
n
n
Pr2
dAF
Defrost delay after fast freezing
0 ÷ 23h 50 min.
2
2.0
Pr2
dFP
End defrost probe for first evaporator
nP; P1, P2, P3
- - -
P2
Pr2
dSP
End defrost probe for second evaporator
nP; P1, P2, P3
- - -
nP
Pr2
FANS
FnC
Fans operating mode
C-n, C-y, O-n, O-y
O-n
O-n
Pr2
Fnd
Fans delay after defrost
0÷255 min.
10
10
Pr2
FSt
Fans stop temperature
-50,0÷110°C / -58÷230°F
2.0
2.0
Pr2
FAP
Fan probe selection
nP; P1, P2, P3
nP
P2
Pr2
ALARMS
ALC
Temperature alarms configuration
rE÷Ab
rE
rE
Pr2
ALU
MAXIMUM temperature alarm
-50,0÷110°C/-58÷230°F
10.0
10.0
Pr1
ALL
minimum temperature alarm
-50,0÷110°C/ -58÷230°F
10.0
10.0
Pr1
AFH
Temperature alarm and fan differential
0,1÷25,5 °C/ 1÷45°F
2.0
2.0
Pr2
ALd
Temperature alarm delay
0÷255 min.
15
15
Pr2
dAO
Delay of temperature alarm at start up
0 ÷ 23h 50 min.
1.3
1.3
Pr2
EdA
Alarm delay at the end of defrost
0÷255 min.
30
30
Pr2
dot
Delay of temperature alarm after closing the door
0÷255 min.
15
15
Pr2
dOA
Open door alarm delay
0÷254 min.,nu
15
15
Pr2
rrd
Regulation restart after door open alarm
y ÷ n
y
y
Pr2
tBA
Alarm relay silencing
y ÷ n
y
y
Pr2
nPS
Pressure switch activation number
0÷15
0
0
Pr2
ANALOGUE INPUTS
Ot
Thermostat probe calibration
-12,0÷12,0°C / -21÷21°F
0
0.0
Pr1
OE
Evaporator probe calibration
-12,0÷12,0°C / -21÷21°F
- - -
0.0
Pr2
O3
Auxiliary probe calibration
-12,0÷12,0°C / -21÷21°F
0
0.0
Pr2
P2P
Evaporator probe presence
n ÷ y
- - -
y
Pr2
P3P
Auxiliary probe presence
n ÷ y
n
n
Pr2
Pbr
Regulation probe selection
P1, P2, P3, 1r2
P1
P1
Pr2