1164/1164NS Series Installation and Programming Guide 6
SELECT A LOCATION
Use the LED survey operation to select a proper location for the smoke detector. The LED
survey operation allows one person to confirm communication with the wireless receiver
or panel while the cover is removed. Because the smoke detector’s transmitter LED is not
visible, use a separate 1100 Series transmitter for the LED survey operation, such as the
1106 Universal Transmitter.
1. Hold the 1106 in the exact desired location.
2. Press the tamper switch on the 1106 to send data to the panel and determine if
communication is confirmed or faulty.
Confirmed: If communication is confirmed, for each press or release of the
tamper switch the LED blinks immediately on and immediately o.
Faulty: If communication is faulty, the LED remains on for up to eight
seconds or flashes multiple times in a quick succession. Relocate the wireless
receiver until the LED confirms clear communication.