Alarms Power+ n˚1
Manual
Immediate
Yes
Turns off
compressor
Check the load
Check network control devices and cables
Check the input voltage and rectify the
trouble.
Using a 1000 V megger, check the motor and
motor cables for ground faults.
Check the input and output circuits for phase
loss detection and rectify.
Check the condition of the motor and load
wiring.
16:Drive disabled
17:Motor Phase
18:Fan Fault
19:Speed Fault
20:PFC Failure
21:Overvoltage
22:Undervoltage
23:STO Detection
24:Reserved
25:Ground Fault
26:CPU Sync 1
27:CPU Sync 2
28:Drive overload
29:Reserved
99:Unexpected inverter stop