65
Cond Setpoint
36
36
36
Deg F
Cond Band
2.7
2.7
2.7
Deg F
Comp Speed
60
40
40
RPS
Compressor PID
Cntrl
P
P
P
K
20
20
20
Int
0
0
0
Seconds
Alarm Setups
CW High Temp Limit
Setpoint
125
125
125
Deg F
Off Band (SP-)
15
15
15
Deg F
Retries
3
3
3
Retry delay
30
30
30
Minutes
CW Freeze Limit
Setpoint
38
38
38
Deg F
Off Band (SP+)
5.4
5.4
5.4
Deg F
Retries
3
3
3
Retry delay
10
10
10
Minutes
CW Flow
10
10
10
Seconds
Retries
3
3
3
Retry delay
10
10
10
Minutes
High Discharge Pressure
550
550
550
PSI
Retries
3
3
3
Retry delay
30
30
30
Minutes
High Pressure Switch
Retry
3
3
3
Retry delay
30
30
30
Minutes
Low Suction Alarm
Low Suction Pressure Cool
60
60
60
PSI
Low Suction Pressure Heat
60
60
60
PSI
Delay
180
180
180
Seconds
Retries
3
3
3
Retry delay
30
30
30
Minutes
Inverter Alarms
Retry
15
15
15
Retry delay
60
60
60
Minutes
Disable
300
300
300
Seconds
Configuration Menu
Temperature Units
Deg F
Deg F
Deg F
Pressure Units
PSI
PSI
PSI