CX9230
Recipro/Scroll(Chiller) Controller
REV DATE
R20180403
- 12 -
4.3 SCHEDULE
4.4 LOG
4.5 MAINTENANCE
4.6 TRIP
NO
Parameter
Run
Stop
View
Access
Description
200
SUN RUN~STOP
00:00
00:00
FREE
FREE
201
MON RUN~STOP
08:00
18:00
FREE
FREE
202
TUE RUN~STOP
08:00
18:00
FREE
FREE
203
WED RUN~STOP
08:00
18:00
FREE
FREE
204
THU RUN~STOP
08:00
18:00
FREE
FREE
205
FRI RUN~STOP
08:00
18:00
FREE
FREE
206
SAT RUN~STOP
08:00
18:00
FREE
FREE
NO
Date
Time
.Occur/Reset
Event
1
YY / MM / DD
HH : MM
(Occur)
Event #1
2
YY / MM / DD
HH : MM
(Occur)
Event #2
3
YY / MM / DD
HH : MM
(Occur)
Event #3
l
YY / MM / DD
HH : MM
(Occur)
Event #4
50
YY / MM / DD
HH : MM
(Occur)
Event #50
NO
Parameter
Default
Min.
Max.
View
Access
Description
400
SENSOR CHECK
0
32000
FREE
SERVICE
401
SAFETY PARTS
0
32000
FREE
SERVICE
402
ELECTRIC PARTS
0
32000
FREE
SERVICE
403
COMP. PARTS
0
32000
FREE
SERVICE
404
REFERIGERANT
0
32000
FREE
SERVICE
405
OVERHAUL
0
32000
FREE
SERVICE
NO
Parameter
Default
Min.
Max.
View
Access
Description
4 0101
FLOW DETECT DLY
10Sec
0
999
USER
SERVICE
Flow detection alarm will detected after
pump start and the lapse of flow detection
delay time
4 0102
FLOW DETECT TIME
3Sec
0
99
USER
SERVICE
If flow detection signal detects status of
without flow continuously, alarm will occur.
Flow detection fault, alarm will occur (Comp.
stops immediately)
4 0103
LP ALARM MODE
1
0
3
USER
SERVICE
0=Unuse:
1=Auto-Reset:
2=Checkd-Reset:
3=Forced-Reset:
4 0104
LP ALARM PRESS.
2.5bar
-1.0
99.9
USER
SERVICE
In case of setting USE in LO-PRESS. SENSOR
[1104], input the lower limit of low pressure
detection.
4 0105
LP ALARM RESET
3.5bar
-1.0
99.9
USER
SERVICE
In case of setting USE in LO-PRESS. SENSOR

Related product manuals