25
2 MAINTENANCE
PLC MAINTENANCE - continued
MULTICYCLE COUNTER SELECTION
STEPS DIRECTIONS
1 Press the Menu Button
2 Press Arrow Down Button to select PARAMETER (flashing)
3 Press Menu/Ok Button
4 Press Arrow Up Button until CC2 (flashing)
5 Press Arrow Left Button until P=0001 is (flashing)
6 Press Arrow Down or Arrow Down to select cycle count*
7 Press Menu/Ok Button
8 Press Menu/Ok Button with YES to Confirm Changes
9 Press the Menu Button
TIMER SETTINGS (in seconds)
MODEL NO. RAM STOP REAR RAM STOP FORWARD
TT1 TT2 TT1 TT2
RJ-88SC 27 17 17 27
RJ-100SC 21 16 16 21
RJ-250SC 19 13 13 19
RJ-250 Ultra 19 13 13 19
Ram Stop Rear or Ram Stop Forward Selection
STEPS DIRECTIONS
1 Press & Hold the Arrow Left Button to Change and display the current ram stop position
NOTE: Repeating this process switches the current postion to ram stop forward or ram stop reverse.
PLC MAINTENANCE - EXTEND/RETRACT TIMER ADJUSTMENT
STEPS DIRECTIONS
1 Press the Menu Button
2 Press the Up or Down Arrow Button until you get to PARAMETER
3 Press the Menu Button
4 Press the Up or Down Arrow Button until TT1 is flashing (Extend Timer)
5 Press the < Arrow Button
6 Press the Up or Down Arrow Button until the desired time is flashing
7 Press Menu
8 Press Menu with YES blinking
9 Repeat Steps 4-8 with TT2 (Retract Timer)
10 Press the Menu Button to return to normal operation.