Rack Monitor 88XX
Document: Installation Manual
Date: January 2024
Version: A.0 subject to change
Page 13 of 30 Installation Manual
1.8 Installation Rack Monitor 88XX
Installation & maintenance shall be carried out in accordance with the applicable code of practice by suitable
trained personnel.
Steps to mount the Rack Monitor 88XX:
Remove the Rack Monitor 88XX from the box and make sure it is free from damages,
Check if the Rack Monitor 88XX corresponds to the drawing in Figure 2.
Figure 2
Remove the 14 bolts mounted into the lid,
Remove the lid and pay extra attention to the plastic
screen mounted on the rear of the lid.
The plastic screen is part of the flame-path of the
housing,
Warning: Store the lid on a clean surface with.
Front faced downwards.
Mounting Holes
Drawing at right shows the dimensions
of the mounting holes
Figure 3
Sil
270.00 mm (10.63")
230.00 mm (9.06")
60.02 mm (2.36")
19.0 mm
(0.75")
45.0 mm
(1.77")
M20 x 1.5 (88xxE Models)
Typical 5 Places
6 mm
40.0 mm
(1.58")
Ground
40.0 mm
(1.58")
40.0 mm
(1.58")
40.0 mm
(1.58")
Stud
1/2"-14 NPT (88xxN Models)