Rack Monitor 88XX
Document: Installation Manual
Date: January 2024
Version: A.0 subject to change
Page 25 of 30 – Installation Manual
6 Trouble Shooting
Not all events can be displayed and please consult the operational manual for operational related problems.
On all relay contacts and power inlet voltage terminal suppressors are placed to limit the surge voltage and current
as well absorbing energy. The surge protecting devices protect the rack input voltage and relay contacts against
surges generated by electromagnetic effects such as lightning or electrostatic discharge, over-voltages and high
inductive loads. If a device is overloaded it can explode during the protection process. Consult OPW if this has
happened.
Do NOT replace fuses if the reason of a blown fuse is unknown.
Caution: When replacing the fuses, always make sure that you replace the fuse with original
ones with an equal stated value.
7 Procedure in case of an Error or Emergencies
Many events could happen when working or installing a Rack Monitor, please see below summary showing a
selection of potential events and errors and the proposed solutions.
Important: in case of personal injury the local medical services are contacted immediately. OPW Engineered
Systems cannot being held responsible for none, late or erroneously medical care.
When there is no personal injury but there is a high risk of explosions, fire or environmental disorders the local
authorities should and must be contacted before contacting the OPW Engineered Systems.
Not all bolts can be applied to
mount the enclosure to its
designated position.
Check whether the drill pattern
is right.
-Correct the hole pattern
-Check if the bolts are M8x65
The Rack Monitor 88XX doesn’t
turn ON
The mains connector isn’t
connected.
Connect the mains connector.
Check if the main wiring is
connected according to the
installation instruction.
Check if there is any power
available at the terminal of the
Rack Monitor 88XX.
Replace the fuses for new ones.
The door cannot being closed
There is a cable between the
door and the back of the
enclosure
Remove the cable (bend it the
other way) and try to close the
door again.
System goes directly into ‘NON
PERMISSIVE’
The Deadman switch is not
connected.
Connect the cable according to the
installation manual.
Connect a bypass cable between
pin 1 & 2 according to the
installation manual.
For all other possible inflictions/damages to the Rack Monitor 88XX, contact OPW Engineered Systems and
ask for assistance.