24
Split Phase
When making split phase measurements, use both channels A and C for
voltage and current connections. The Neutral is chosen as the reference
for measurement purposes. You may optionally measure the Neutral
current by connecting a current probe to the Neutral conductor and to the
N channel current input.
NOTE Be sure to connect the current probes with the arrow
pointing towards the load or an erroneous power reading
will result.