07-01776H F412-115V 11 Dri-Eaz Products, Inc.
TROUBLESHOOTING
Water drips out
when moving unit
Unit was unplugged before
purging was complete.
Purge unit before moving. See “At the End of the Job,” p. 5.
Plug in unit; check power cord connection at wall outlet and at
base of unit.
Remove duct ring and grill and remove obstruction. Replace
duct ring and grill.
Unit operating,
but room not dry
Poor air movement in room.
Excessive moist air infiltration.
Allow more time for drying.
Increase air movement with air movers.
Seal off area to reduce infiltration.
Unit collects too
little water
Room temperature is too low.
HAF filter is full.
Heat exchange block and/or
coils are clogged.
Confirm humidity level with hygrometer.
Increase room temperature.
Check filter. Clean or replace as necessary.
Check heat exchange block and coils. Clean as necessary.
If the problem you are experiencing is not listed here, call your local distributor or contact
our Service Department toll-free at 800-932-3030 for further assistance.
SPECIFICATIONS
33.5 × 20 × 20 in. | 85 × 51 × 51 cm
Water removal AHAM
(80°F/60% RH)
130 pts. | 61.5 liters / day
Water removal low grain
(80°F/20% RH)
325 CFM* ductable floor-level outlet.
3M™ HAF filter
Part no. F368 (24 pack)
ETL certified CSA 22.2 no. 92
Specifications are subject to change without notice. Some values
may be approximate.
*Fan speed varies automatically for optimized performance.
Warranty information is available at www.dri-eaz.com.
Be sure to visit warranty.drieaz.com and register your
purchase. Your registration will help us provide you with
updated product information as needed.
For proper disposal, this unit should be taken to a
recycler licensed to process refrigeration equipment.