07-01776H F412-115V 9 Dri-Eaz Products, Inc.
SYSTEM MESSAGES
The Control Panel will display the following messages based on system performance and environmental conditions. User
action, if any is required, is indicated in the third column.
C O N T R O L P A N E L
M E S S A G E
Indicates control board firmware version number.
Unit has finished powering up and is operating.
60s delay before compressor turns on. Allows system
pressure to equalize.
First line: indicates total operating hours.
Second line: Toggles between inlet temperature and
inlet RH every 2 seconds.
First line: indicates unit is in humidistat mode
Second line: Toggles between inlet temperature and
inlet RH every 2 seconds.
F515 only. Unit shuts off if inlet temp below 45° F.
Turns back on when inlet reaches 50° F.
Unit overload limit reached. Cool-down initiated.
Unit is defrosting, with countdown in seconds.
Unit turned off when coil is cold or already in a defrost
cycle. Proceeds to finish cycle or initiate one to clear
the coils of ice before storage.
Occurs when unit is turned off and coil is not frozen.
Clears the coils of water before storage.
Prompt to clean or change filter.
Change or clean filter. Press
the > key to reset
Prompt to clean coils and interior.
Clean coils. Press the > key
to reset