36
RTS HUMIDIFIER RX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
If the ambient temperature in the enclosure is below 50 ºF (10 ºC), the heater is
powered up. The heater remains powered up until the enclosure reaches
60 ºF (15.5 ºC). When there is no call for humidity, an aquastat maintains tank
temperature at the factory default of 50 ºF (10 ºC). This temperature can be
reset in the field to be from 50-180 ºF (10-82 ºC). If for any reason the tank
temperature falls below 40 ºF (4 ºC), the tank will drain to keep the unit from
freezing.
When the temperature of the enclosure reaches 85 ºF (29 ºC), the ventilation
fans turn on to cool the electronic components. If the enclosure temperature
reaches 150 ºF (66 ºC), the Vapor-logic controller will disable any heating
elements and allow the ventilation fans to cool the enclosure. When the
enclosure temperature falls below 150 ºF (66 ºC), the RTS humidifier
automatically resumes normal operation.
In the event of a power loss, the drain valve will open and drain the tank
to prevent the water from freezing. The water will be cooled by the integral
mechanical drain water tempering.
Outdoor enclosure: Operation