PC3000 Version 7.7
[17] Zone Definitions for Zones 9 to 16
Page 17
Note: Zones 9-16 cannot be programmed for fast response - Do not use fast response devices on these loops.
e.g. Vibration detectors.
Default 1st Digit 2nd Digit
0 1 Zone 9 0 = Slow, audible 0 = Delay
0 1
Zone 10 1 = Slow, silent 1 = Instant
0 1 Zone 11 2 = Interior
0 1
Zone 12 3 = Interior...Home-Away
0 1 Zone 13 4 = 24 hr...Bell
0 1 Zone 14 5 = 24 hr...Bell/Buzzer
0 1
Zone 15 6 = 24 hr...Buzzer
0 1 Zone 16 7 = Double delay
8 = 4x Delay
9 = Day
A = Delay...Home-Away
[18] 1st System Option Code
Page 17
Default Zone Light On Zone Light Off
Off
Zone Light 1 ......................... Communication disabled Communication enabled
Off Zone Light 2 ......................... Restorals on bell timeout Restorals on disarming
Off Zone Light 3 ......................... Alarm display while armed No alarm display/armed
Off
Zone Light 4 ......................... DTMF dialing Pulse dialing
Off Zone Light 5 ......................... N/C loops EOL resistors loops
Off
Zone Light 6 ......................... Keypad [P]anic audible Silent
On Zone Light 7 ......................... Call 1st phone only Back up to 2nd phone
Off Zone Light 8 ......................... 16th code = maid's code Normal code
[19] 2nd System Option Code
Page 18
Default Zone Light On Zone Light Off
Off Zone Light 1 ......................... Bell pulses always Bell pulses upon fire only
Off Zone Light 2 ......................... Master code not changeable Master code changeable
Off
Zone Light 3 ......................... Bell squawk enabled Bell squawk disabled
Off Zone Light 4 ......................... PC16 OUT enabled PC16 OUT disabled
Off Zone Light 5 ......................... TLM trouble only TLM audible when armed
Off
Zone Light 6 ......................... 1400Hz Radionics 2300Hz Radionics
Off Zone Light 7 ......................... TLM disabled TLM enabled
Off
Zone Light 8 ......................... Access code req'd for bypass Access code not req'd
WWW.DIYALARMFORUM.COM