CONFIGURABLE INPUTS
Input channel Polarity Type Activation time
Remote start Close to activate
Low oil pressure Close to activate Shutdown Active from safety on
High engine temp. Close to activate Shutdown Active from safety on
Auxiliary input 1 Close to activate Warning Always active
Auxiliary input 2 Close to activate Warning Active from safety on
Auxiliary input 3 Close to activate Shutdown Active from safety on
Auxiliary input 4 Close to activate Indication Always active
RELAY OUTPUTS
Output channel Polarity Control source
Auxiliary output 1 Energize 1 Pre-heat
Auxiliary output 2 Energize 18 Common alarm
Auxiliary output 3 Energize 4 Load transfer
FRONT PANEL LED'S
LED Polarity Control source
LED 1 Lit 25 Remote start present
LED 2 Lit 21 Charge fail alarm
LED 3 Lit 18 Common alarm
LED 4 Lit 20 Overspeed alarm
LED 5 Lit 7 Fail to start alarm
LED 6 Lit 28 High engine temp. Alarm
LED 7 Lit 27 Low oil pressure alarm
LED 8 Lit 32 Auxiliary IP 4 active
LED 9 Lit 31 Auxiliary IP 3 active
LED 10 Lit 30 Auxiliary IP 2 active
LED 11 Lit 29 Auxiliary IP 1 active
SYSTEM TIMERS
Timer Mins:secs
Remote start delay time 0:05
Remote stop delay time 0:30
Cranking time 0:10
Crank rest time 0:10
Safety on delay time 0:10
Warm up time 0:05
Cooling time 0:30
Fail to stop time 0:30
ETS hold time 0:00
Pre-heat time 0:00
Sensor fail delay time 0:02
Smoke limiting time 0:00
Smoke limiting ramp time 0:00
ANALOGUE LEVELS
Level Value
Overspeed on alternator frequency 57.0 Hz
Overspeed on magnetic pickup 1750 RPM
Overspeed overshoot during safety on delay 0 %
Underspeed on alternator frequency 30.0 Hz
Underspeed on magnetic pickup 1250 RPM
Crank disconnect on alternator frequency 21.0 Hz
Crank disconnect on magnetic pickup 600 RPM
Crank disconnect charge alternator voltage 30.0 V
Charge fail voltage 8.0 V