056-051 Gencomm Control Keys Issue 3 – A.D.Manton
Function
code
System control function
System control
key
(decimal)
Ones compliment
of control key
(65535-control
key)
54-59 Reserved
60 SMS run on load signal (88xx/84xx only) - sent by the display
processor to the control processor to signal when an SMS
command to run the generator on load has been received
35760 29775
61 SMS run off load signal (88xx/84xx only) - sent by the display
processor to the control processor to signal when an SMS
command to run the generator off load has been received
35761 29774
62 SMS request auto mode (88xx/84xx only) - sent by the display
processor to the control processor to signal when an SMS
command to change to auto mode has been received
35762 29773
63 SMS request stop mode (88xx/84xx only) - sent by the display
processor to the control processor to signal when an SMS
command to change to stop mode has been received
35763 29772
64 SMS request clear run mode (88xx/84xx only) - sent by the
display processor to the control processor to signal when an SMS
command to clear the run request has been received
35764 29771
65 SMS run in island mode signal (8820/8860/8420 only) - sent by
the display processor to the control processor to signal when an
SMS command to run the generator in island mode has been
received
35765 29770
66 Reset battery maintenance alarm 1 35766 29769
67 Reset battery maintenance alarm 2 35767 29768
68 Reset battery maintenance alarm 3 35768 29767
69 Auto DPF regeneration inhibit on 35769 29766
70 Auto DPF regeneration inhibit off 35770 29765
71 Start manual DPF regeneration 35771 29764
72 Battery Charger Boost Mode 35772 29763
73 Battery Charger Stop Charging 35773 29762
74 Battery Charger Battery Test 35774 29761
75 Battery Charger Select Alternative Charging Voltage 35775 29760
76 Select Off Mode 35776 29759
77 Throttle Down 35777 29758
78 Throttle Up 35778 29757
79 Wake ECU 35779 29756
80 Lamp Test 35780 29755
81 Battery Charger Auxiliary Boost Mode 35781 29754
82 Battery Charger Auxiliary Stop Charging 35782 29753
83 Battery Charger Auxiliary Battery Test 35783 29752
84 Battery Charger Auxiliary Select Alternative Charging Voltage 35784 29751
85-65535 Reserved